Plan Review Notes
Plan Review Notes For Permit 99090934
Permit Number 99090934
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00NEEDS COUNTY IMPACT FEES PAID
 PLAN #2, THE DESIGN CRITERIA STATED IS
 INVALID.
 PROVIDE A DESIGN COMPLIANCE FORM. SEE
 ATTACHED
 PROVIDE A LEDGIBLE SHOP DRAWINGS FOR THE
 STORM PANELS. COPIES TO SHOW ENTIRE PAGE
 THE KINCO LTD SLIDING GLASS DOOR SHOP
 DRAWING DOES NOT REFERENCE THE VALID
 BUILDING CODE.
 PROVIDE A DETAIL FOR THE CMU BEAM AT THE
 STEP UP.
 SPECIFY THE ABOVE & BELOW GRADE DIMENSIO
 FOR THE MONO FOOTER IN THE TYP WALL SECT