Plan Review Notes
Plan Review Notes For Permit 99090749
Permit Number 99090749
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 AHU'S WITH LESS THAN 2000 CFM BUT SERVIN
 G AREAS USED FOR EGRESS SHALL HAVE FAN
 SHUT DOWN BY DUCT SMOKE DETECTOR
 PER 1997 SMC 406
 NOTIFICATION OF FAN SHUT DOWN TO BE TIED
 TO BLDG FIRE ALARM OR HORN AND STROBE
 PER NFPA 90A 4-4.4.2 OR .3