2001-01-08 00:00:00REVISED M-1 AND M-2 DRAWINGS
 PROVISO: A/C UNIT SERVING CORRIDOR AREA
 TO HAVE FAN SHUT DOWN BY DUCT SMOKE DET-
 ECTOR OR SHUT DOWN WITH AREA SMOKES(BLDG
 FIRE ALARM) PER 1997 SMC 406.2 AREAS
 WITH LESS THAN 2000 CFM BUT SERVING AN
 AREA USED FOR EGRESS.