Plan Review Notes For Permit 99090717 |
Permit Number |
99090717 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO***************** | | OUTLET TEE FROM GREASE TRAP SHALL EXTEND | | TO WITHIN 8" OF BOTTOM OF TANK.DOH RULE | | 64E-6.013(5). | | | | SHTS.P-1,P-2-BAR SINKS CANNOT DISCHARGE | | INTO SANITARY SYSTEM.MUST DISCHARGE THRU | | GREASE INTERCEPTOR PER SPC SEC.1004.3. | | | | CHECK DIMENSIONS FOR GREASE TRAPS AS | | LISTED ON SHT.P-2,NOTE #4. | | (5X10X6=300 CU.FT.X 7.5 GALS PER CU.FT.= | | 2250 GALS.) | | | | ________________________________________ | | SHTS.P-1,P-2,P-3,-REVISE SANITARY AND | | PIPE SIZES,REVISE CONDENSATE SYSTEM, | | REVISE WATER PIPING LAYOUT AND SIZES. |
|