Plan Review Notes
Plan Review Notes For Permit 99090717
Permit Number 99090717
Review Stop P
Sequence Number 4
Notes
Date Text
2001-01-08 00:00:00****************PROVISO*****************
 OUTLET TEE FROM GREASE TRAP SHALL EXTEND
 TO WITHIN 8" OF BOTTOM OF TANK.DOH RULE
 64E-6.013(5).
  
 SHTS.P-1,P-2-BAR SINKS CANNOT DISCHARGE
 INTO SANITARY SYSTEM.MUST DISCHARGE THRU
 GREASE INTERCEPTOR PER SPC SEC.1004.3.
  
 CHECK DIMENSIONS FOR GREASE TRAPS AS
 LISTED ON SHT.P-2,NOTE #4.
 (5X10X6=300 CU.FT.X 7.5 GALS PER CU.FT.=
 2250 GALS.)
  
 ________________________________________
 SHTS.P-1,P-2,P-3,-REVISE SANITARY AND
 PIPE SIZES,REVISE CONDENSATE SYSTEM,
 REVISE WATER PIPING LAYOUT AND SIZES.