2001-01-08 00:00:00SHT.P-2-CONDENSATE DRAINS SHALL NOT BE
 DIRECTLY CONNECTED TO THE STORM DRAINAGE
 SYSTEM PER SPC SEC.804.3.
  
 SHT.P-2-NOTES BAR SINKS/LAVS CONNECTED
 TO SANITARY SYSTEM.FIXTURES IN KITCHEN
 AREA EXCEPT DISHWASHER SHALL DISCHARGE
 INTO THE GREASY WASTE SYSTEM.SPC SEC.
 804.1.,1004.4.
  
 TWO WAY CLEANOUTS ARE REQD.ON THE INLET
 AND OUTLET OF THE GREASE INTERCEPTORS.
 SPC SEC.710.4.
  
 BRANCH LINES SHALL BE VALVED PER SPC
 610.4.2.(SEE NOTED AREAS ON PLANS.)
  
 SHT.P-4-NOTE #1-STATES DISHWASHER TO
 DISCHARGE INTO SANITARY.REVISE NOTE.
 DISHWASHER SHALL DISCHARGE TO SANITARY
 PER CITY OF WEST PALM BEACH ORDINANCE.
  
 CHECK DIMENSIONS AND CORRESPONDING
 CAPACITIES OF GREASE TRAPS.CAPACITY IN
 GALS.AND DIMENSIONS DON'T CORRELATE.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1