Plan Review Notes
Plan Review Notes For Permit 99090717
Permit Number 99090717
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHT.P-1 NOTES BAR SINKS CONNECTED TO
 SANITARY SYSTEM.SINKS SHALL CONNECT TO
 GREASY WASTE SYSTEM PER SPC SEC.1004.4.
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED.
 COMPLY W/SPC SEC.901.2.
  
 CONTACT RODNEY COMPO AT CITY OF WEST
 PALM BEACH REGIONAL WASTEWATER TREATMENT
 PLANT FOR PROPER SIZINGOF GREASE TRAP.
 (PHONE # 835-7423.
  
 CLEARLY SHOW LOCATION OF G/T ON PLANS.
 AND DISTANCE FROM BUILDING.EXCAVATION
 SHALL COMPLY W/SBC SEC.1803.
  
 SHT.P-2.NOTE #10-TYPE"M" COPPER NOT
 PERMITTED U/G PER COUNTYWIDE AMENDMENTS
 TO BUILDING SEC.611.2.
  
 HOSE BIBBS SHALL BE VALVED PER SPC SEC.
 610.4.1.
  
 SHT.G-1.-GAS PIPE SHALL NOT BE INSTALLED
 UNDER BLDG.PER STD.GAS CODE SEC.308.3