Date |
Text |
2001-01-08 00:00:00 | SHT.A-15-UNIT"C"-A MIN.60" DIAMETER |
| TURNING SPACE MUST BE PROVIDED IN A "U" |
| SHAPED KITCHEN W/A RANGE AT THE BASE PER |
| FAIR HOUSING ACT 24 CFR 100.205 (3)(C) |
| (IV) |
| |
| SHT.A-10 AND A-48-SCUPPER SIZES DON'T |
| MATCH.SUBMIT CALCULATIONS FOR SCUPPERS |
| TO COMPLY W/APPENDIX "A" OF SPC.SHOW |
| SQ.FOOTAGE DRAINED BY EACH SCUPPER. |
| |
| DRINKING FOUNTAINS ARE REQD.IN THE |
| LEASING OFFICE AND THE FITNESS CENTER |
| PER SPC TABLE 407. |
| |
| SHT.A-52-H.C.URINAL SHALL BE SET AT 17" |
| A.F.F.TO THE RIM PER FACBC SEC.4.18. |
| |
| A MIN. OF 29" IS REQD.UNDER H.C.LAV.FROM |
| FINISH FLOOR TO BOTTOM OF APRON PER |
| FACBC SEC.4.19.2. |
| |
| SHT.P-5-MIN.SIZE OF WTR.SUPPLY TO URINAL |
| SHALL BE 3/4" PER TABLE 607 0F SPC. |
| |
| SHT.P-14-STACK #45-FIXTURE BRANCHES AND |
| WATER CLOSETS NOT PERMITTED ON WET VENTS |
| PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| 911.1.1. |
| |
| SHT.P-14-MIN.SIZE OF LOWEST WET VENT |
| SHALL COMPLY W/SPC 911.3 AND TABLE 911.3 |
| (SEE STACKS #45,49,79.) |
| |
| SHT.P-15-SHOWS PAN DRAINS AS 3/4" AND AS |
| 1".CLARIFY. |
| |
| SHT.P-7-50% OF THE AREA OF THE VERTICAL |
| WALL SHALL BE ADDED INTO THE PROJECTED |
| ROOF AREA FOR INCLUSION INCALCULATING |
| SIZE OF STORM DRAINAGE SYSTEM PER SPC |
| SEC.1108.3. |
| |
| 3" FLOOR DRAIN IN TRASH ROOM ON P-2 NOT |
| SHOWN ON SANITARY RISER DIAGRAM. |
| |
| *******************NOTE***************** |
| THE PRECEDING COMMENTS ARE TYPICAL FOR |
| ALL BUILDING TYPES. |