Plan Review Notes
Plan Review Notes For Permit 99090704
Permit Number 99090704
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SHT.A-15-UNIT"C"-A MIN.60" DIAMETER
 TURNING SPACE MUST BE PROVIDED IN A "U"
 SHAPED KITCHEN W/A RANGE AT THE BASE PER
 FAIR HOUSING ACT 24 CFR 100.205 (3)(C)
 (IV)
  
 SHT.A-10 AND A-48-SCUPPER SIZES DON'T
 MATCH.SUBMIT CALCULATIONS FOR SCUPPERS
 TO COMPLY W/APPENDIX "A" OF SPC.SHOW
 SQ.FOOTAGE DRAINED BY EACH SCUPPER.
  
 DRINKING FOUNTAINS ARE REQD.IN THE
 LEASING OFFICE AND THE FITNESS CENTER
 PER SPC TABLE 407.
  
 SHT.A-52-H.C.URINAL SHALL BE SET AT 17"
 A.F.F.TO THE RIM PER FACBC SEC.4.18.
  
 A MIN. OF 29" IS REQD.UNDER H.C.LAV.FROM
 FINISH FLOOR TO BOTTOM OF APRON PER
 FACBC SEC.4.19.2.
  
 SHT.P-5-MIN.SIZE OF WTR.SUPPLY TO URINAL
 SHALL BE 3/4" PER TABLE 607 0F SPC.
  
 SHT.P-14-STACK #45-FIXTURE BRANCHES AND
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 PER COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 SHT.P-14-MIN.SIZE OF LOWEST WET VENT
 SHALL COMPLY W/SPC 911.3 AND TABLE 911.3
 (SEE STACKS #45,49,79.)
  
 SHT.P-15-SHOWS PAN DRAINS AS 3/4" AND AS
 1".CLARIFY.
  
 SHT.P-7-50% OF THE AREA OF THE VERTICAL
 WALL SHALL BE ADDED INTO THE PROJECTED
 ROOF AREA FOR INCLUSION INCALCULATING
 SIZE OF STORM DRAINAGE SYSTEM PER SPC
 SEC.1108.3.
  
 3" FLOOR DRAIN IN TRASH ROOM ON P-2 NOT
 SHOWN ON SANITARY RISER DIAGRAM.
  
 *******************NOTE*****************
 THE PRECEDING COMMENTS ARE TYPICAL FOR
 ALL BUILDING TYPES.