Plan Review Notes
Plan Review Notes For Permit 99090704
Permit Number 99090704
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUPPLY DETAILS FOR SECONDARY ROOF
 DRAINAGE PER SBC SEC.1517.6.4.3.,1604.6.
 SPC 1109.(DETAILS FOR SCUPPERS NOT
 PROVIDED.)
  
 SUBMIT ISOMETRIC FOR STORM DRAINAGE
 SYSTEM.NOTE AREA DRAINED BY EACH R.D.
 COMPLY W/SPC SEC.1108.1,TABLES 1108.1,
 1108.2.AND SLOPE OF PIPE.
  
 CLEARLY SHOW THAT BASE CABINET IN KIT.
 IS OF A REMOVABLE TYPE OR SHOW KNEE
 SPACE IN COMPLIANCE W/FEDERAL FAIR
 HOUSING ACT REQ..# 7.(FOR U-SHAPED
 KITCHENS)
  
 SUBMIT DETAIL OF WATER FILL LINE FOR
 FOUNTAINS.SUPPLY TO BE PROTECTED AGAINST
 BACKFLOW PER SPC SEC.606.
  
 FLOOR PLAN SHOWS 1 1/2" DP DRAIN AND
 RISER SHOWS 1 1/4".COMPLY W/COUNTYWIDE
 AMENDMENTS TO SPC SEC.507.8.3.(SEE
 ATTACHED.)REFER TO SHTS.P-2,P-5,P-11.
  
 3" FLOOR DRAIN TO TRASH ROOM ON P-2 NOT
 ON RISER ON P-3.SPC 104.2.1.
  
 SHT.P-12-UNITS "B"AND "D2"-OVER 4
 FIXTURES ARE CONNECTED TO A 1/2" H.W.
 LINE.COMPLY W/ COUNTYWIDE AMENDMENTS TO
 SPC SEC.607.7.
  
 SHT.P-12-UNIT "C"-OVER 2 FIXTURES ARE
 CONNECTED TO A 1/2" C.W.LINE.COMPLY W/
 COUNTYWIDE AMENDMENTS TO SPC SEC.607.7
  
 SHT.P-13-UNIT F-OVER 4 FIXTURES ARE
 CONNECTED TO 1/2" H.W.
  
 SHT.P-14-STACK #19-SHALL BE 4"PER SPC
 SEC.911.4 & TABLE 911.4.(BRANCH SHALL
 REMAIN FULL SIZE BEGINNING AT HOUSE
 DRAIN.)
  
 SHT.P-14-STACKS # 7,8,38,34-LAV.CANNOT
 CONNECT TO MAIN STACK AND DRY VENT NOT
 PERMITTED PER SPC 911.3(3),911.1.
  
 SIZE OF VENT STACKS FOR MULTI-STORY
 BATHROOM GROUPS SHALL COMPLY W/SPC SEC.
 911.3 AND TABLE 911.3.
  
 CLEARLY SHOW TERMINATION/CONNECTION PT.
 OF ELEVATOR SUMP TO DRAINAGE SYSTEM.
 SPC 104.2.1.
  
 SHT.P-15.-DELETE NOTES REFERRING TO
 SFBC.SPC 101.1
  
 CONTACT CITY OF WEST PALM BEACH REGIONAL
 SEWER TREATMENT FACILITY FOR SPECIFIC
 REQS.OF GREASE AND OIL INTERCEPTORS.
 ATTENTION:RODNEY COMPO.
  
 CLEARLY SHOW LOCATION OF GREASE TRAP ON
 PLANS AND ALL ASSOCIATED PIPING.SPC
 104.2.1.
  
 *****************NOTE*******************
 THE PRECEEDING COMMENTS ARE TYPICAL FOR
 ALL BUILDING TYPES.