Plan Review Notes
Plan Review Notes For Permit 99090704
Permit Number 99090704
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001- PG. E-2 SHOWS PANEL HA AS HAVING 60
 SPACES IT SHOULD BE NOTED THAT THIS
 IS TWO 30 CIRCUIT PANELS. 384-16
 2- PG. E-2,E-5,AND E-11 HAVE NO AIC
 RATING SHOWN FOR BRANCH CIRCUITS.
 MAIN AIC RATING IS SHOWN BUT NOT
 THE BRANCH CIRCUIT RATINGS. 110-9
 3- PG. E-4,E-7, AND E-10 SHOW OUTLETS
 FOR SERVICING THE A/C EQUIPMENT ON
 ROOFS.NOTE IT IS A LOCAL AMENDMENT
 THAT THESE OUTLETS ARE FURTHER THAN
 25' AWAY!!210-63
 4- PG.E-5 ELECTRIC ROOM ON 1ST SHOWS NO
 OUTLET FOR SERVICING THE EQUIP.
 5- SUBMIT ALL INFORMATION REQUESTED
 BEFORE 1ST ROUGH INSPECTION