Date |
Text |
2001-01-08 00:00:00 | 1. PLANS MUST BE SPLIT INTO THREE |
| SEPARATE SETS OF THREE SIGNED AND SEALED |
| DOCUMENTS. |
| 2. IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. |
| 3. PROJECT IS A FLORIDA THRESHOLD |
| BUILDING.PROVIDE APPLICATION |
| AND INSPECTION PLAN TO DON NEELY ABO, |
| FOR REVIEW AND APPROVAL. SEE SHEET S-1 |
| NOTE 3. |
| 4. LANDINGS MUST MEET 1997 SBC SECTION |
| 1007.4.2, SEE SHEET A-21, REFERENCE NOTE |
| A-4 BRIDGE NOTE. |
| 5. FIRE SEPARATION RATING, DETAILS AND |
| OPENINGPROTECTION INFORMATION FOR |
| RESIDENTIALTO COMMERCIAL SPACE SEE |
| SHEET A-11AND SHEET A-12 REQUIRE |
| SECTIONS AND FIRE RATINGS. |
| 6. CERTIFICATION OF PLANS AS COMPLYING |
| WITH FLORIDA STATUTE 553.79 AND FEDERAL |
| FAIR HOUSING ACT, AUGUST 1996 AS REVISED |
| APRIL 1998. |
| 7. SHEET A-17 INDICATES THAT A SLOPE |
| STARTS AT THE DOOR, A LANDING IS |
| REQUIRED AT ALL DOORS PRIOR TO STARTING |
| A SLOPE 1997 SBC SECTION 1012.1.3. |
| 8. PRODUCT APPROVAL FOR ALL WINDOWS AND |
| DOORS SBC 1997, 110 MPH WIND LOADS. |
| 9. PRODUCT APPROVAL FOR GLAZING TO |
| SHOW COMPLIANCEWITH IMPACT PROTECTION |
| REQUIREMENTS. |
| 10. FIRE RATING DOORS, DOOR 15, 16, 17, |
| AND 22 REQUIRE B LABEL SHEET A-26 |
| INDICATES C LABEL. |
| 11. DOOR 20 TO EXCERISE ROOM TO BE 20 |
| MINUTE RATED AND DOOR 21 TO OFFICE TO BE |
| 3/4 HR. C LABELED DOOR. |
| 12. SHEET A-27 IF HURRICANE SHUTTERS ARE |
| TO BE USED PROVIDE. A) THE STORAGE |
| LOCATION FOR ALL PANELSREQUIRED AND |
| THE INSTALLATION PLAN FOR REVIEW AND |
| APPROVAL. CHANGE REFERENCE IN NOTE 2 |
| TO 1997 EDITION OF THE SBC AND SSTD |
| 10-97, REFERENCE IS TO THE 1994 CODE AND |
| STANDARD. |
| 13. TRUSS DIAGRAMSFOR THE PROJECT. |
| 14. SHEET A-44 MEET 1997 FLORIDA |
| HANDICAPPED CODE FIGURE 19 FOR STAIR |
| HANDRAILS, PAGE 99. |
| 15. SHEET A-48 CHANGE NOTE TO REFERENCE |
| 1997 SBC FOR ROOFING. |
| 16. POOLS, SUBMIT TO HEALTH DEPT. FOR |
| REVIEW AND APPROVAL, PROVIDE INFORMATION |
| ON FENCING AND GATES AS REQUIRED BY CITY |
| W.P.B. POOL CODE. SHEET A-54 |
| 17. SHEET S-2 ETC. INDICATE SLUMP OF |
| GROUT. |
| |
| 18. ADDITIONAL PERMIT FEES DUE. |
| 19. CODE REFERENCES |
| 1997 STANDARD BUILDING MECHANICAL AND |
| GAS CODES |
| 1996 NATIONAL ELECTRICAL CODE |
| 1994 STANDARD PLUMBING CODE |
| 1997 FLORIDA HANDICAPPED CODE |
| 1997 FLORIDA ENERGY CODE |
| 1996 FEDERAL FAIR HOUSING ACT AS AMENDED |
| CITY OF WEST PALM BEACH AMENDMENTS TO |
| THE CODES EFFECTIVE JULY 1, 1999. |
| |
| 20. CODE REVIEW IS FOR 630, 720 AND 780 |
| SAPODILLA. |