Plan Review Notes
Plan Review Notes For Permit 99090704
Permit Number 99090704
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001. PLANS MUST BE SPLIT INTO THREE
 SEPARATE SETS OF THREE SIGNED AND SEALED
 DOCUMENTS.
 2. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.
 3. PROJECT IS A FLORIDA THRESHOLD
 BUILDING.PROVIDE APPLICATION
 AND INSPECTION PLAN TO DON NEELY ABO,
 FOR REVIEW AND APPROVAL. SEE SHEET S-1
 NOTE 3.
 4. LANDINGS MUST MEET 1997 SBC SECTION
 1007.4.2, SEE SHEET A-21, REFERENCE NOTE
 A-4 BRIDGE NOTE.
 5. FIRE SEPARATION RATING, DETAILS AND
 OPENINGPROTECTION INFORMATION FOR
 RESIDENTIALTO COMMERCIAL SPACE SEE
 SHEET A-11AND SHEET A-12 REQUIRE
 SECTIONS AND FIRE RATINGS.
 6. CERTIFICATION OF PLANS AS COMPLYING
 WITH FLORIDA STATUTE 553.79 AND FEDERAL
 FAIR HOUSING ACT, AUGUST 1996 AS REVISED
 APRIL 1998.
 7. SHEET A-17 INDICATES THAT A SLOPE
 STARTS AT THE DOOR, A LANDING IS
 REQUIRED AT ALL DOORS PRIOR TO STARTING
 A SLOPE 1997 SBC SECTION 1012.1.3.
 8. PRODUCT APPROVAL FOR ALL WINDOWS AND
 DOORS SBC 1997, 110 MPH WIND LOADS.
 9. PRODUCT APPROVAL FOR GLAZING TO
 SHOW COMPLIANCEWITH IMPACT PROTECTION
 REQUIREMENTS.
 10. FIRE RATING DOORS, DOOR 15, 16, 17,
 AND 22 REQUIRE B LABEL SHEET A-26
 INDICATES C LABEL.
 11. DOOR 20 TO EXCERISE ROOM TO BE 20
 MINUTE RATED AND DOOR 21 TO OFFICE TO BE
 3/4 HR. C LABELED DOOR.
 12. SHEET A-27 IF HURRICANE SHUTTERS ARE
 TO BE USED PROVIDE. A) THE STORAGE
 LOCATION FOR ALL PANELSREQUIRED AND
 THE INSTALLATION PLAN FOR REVIEW AND
 APPROVAL. CHANGE REFERENCE IN NOTE 2
 TO 1997 EDITION OF THE SBC AND SSTD
 10-97, REFERENCE IS TO THE 1994 CODE AND
 STANDARD.
 13. TRUSS DIAGRAMSFOR THE PROJECT.
 14. SHEET A-44 MEET 1997 FLORIDA
 HANDICAPPED CODE FIGURE 19 FOR STAIR
 HANDRAILS, PAGE 99.
 15. SHEET A-48 CHANGE NOTE TO REFERENCE
 1997 SBC FOR ROOFING.
 16. POOLS, SUBMIT TO HEALTH DEPT. FOR
 REVIEW AND APPROVAL, PROVIDE INFORMATION
 ON FENCING AND GATES AS REQUIRED BY CITY
 W.P.B. POOL CODE. SHEET A-54
 17. SHEET S-2 ETC. INDICATE SLUMP OF
 GROUT.
  
 18. ADDITIONAL PERMIT FEES DUE.
 19. CODE REFERENCES
 1997 STANDARD BUILDING MECHANICAL AND
 GAS CODES
 1996 NATIONAL ELECTRICAL CODE
 1994 STANDARD PLUMBING CODE
 1997 FLORIDA HANDICAPPED CODE
 1997 FLORIDA ENERGY CODE
 1996 FEDERAL FAIR HOUSING ACT AS AMENDED
 CITY OF WEST PALM BEACH AMENDMENTS TO
 THE CODES EFFECTIVE JULY 1, 1999.
  
 20. CODE REVIEW IS FOR 630, 720 AND 780
 SAPODILLA.