2001-01-08 00:00:00SUBMIT A WATER RISER FOR REVIEW THAT
 CLEARLY REFLECTS THE ENTIRE SCOPE OF
 PLUMBING WORK BEING DONE.SPC 104.2.1.
  
 SUBMIT TOTAL OCCUPANT LOAD OF STRUCTURE
 AND NOTE ON THE PLAN THE NUMBER OF EXIST
 PLUMBING FIXTURES TO ENSURE COMPLIANCE
 W/SPC TABLE 407.
  
 DRINKING FOUNTAIN REQD.PER SPC TABLE 407
  
 SUBMIT DETAILS FOR THE HANDICAP FIXTURES
 ACCESSIBLE TOILET STALLS SHALL COMPLY
 W/FACBC SEC.4.17.3(SEE EXCEPTION:NEW
 CONSTRUCTION).