Plan Review Notes
Plan Review Notes For Permit 99090559
Permit Number 99090559
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************PROVISO******************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF EQUIPMENT AND
 MAIN BRKRS.FIGURED FROM FALUT CURRENT
 CALCULATIONS.
 2)NOTE:AS PER ART 250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GO TO BLDG,STEEL
 ALSO.
 3)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:AS PER 1996/1993 NFPA-72 1996 NEC
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN NEW CON-
 -STRUCTION OF RES.DWELLINGS. 2-2.1.1.1
 5)NOTE:SMOKE DETECTORS ARE TO BE 5`
 FROM RETURN AIR.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 TO BE APPROVED BEFORE FIRST ROUGH
 ELECTRICAL INSPECTION.