Plan Review Notes For Permit 99090559 |
Permit Number |
99090559 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO****************** | | | | 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO | | SUBMIT AIC RATING OF EQUIPMENT AND | | MAIN BRKRS.FIGURED FROM FALUT CURRENT | | CALCULATIONS. | | 2)NOTE:AS PER ART 250-81 GROUNDING | | ELECTRODE CONDUCTOR TO GO TO BLDG,STEEL | | ALSO. | | 3)NOTE:AS PER ART;210-8-A-6 ALL OUTLETS | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | GFI/GFI PROTECTED. | | 4)NOTE:AS PER 1996/1993 NFPA-72 1996 NEC | | SMOKE DETECTORS ARE REQ`D INSIDE AND | | OUTSIDE ALL SLEEPING ROOMS IN NEW CON- | | -STRUCTION OF RES.DWELLINGS. 2-2.1.1.1 | | 5)NOTE:SMOKE DETECTORS ARE TO BE 5` | | FROM RETURN AIR. | | | | NEED TO SUBMIT THE ABOVE INFORMATION | | TO BE APPROVED BEFORE FIRST ROUGH | | ELECTRICAL INSPECTION. |
|