Plan Review Notes
Plan Review Notes For Permit 99090252
Permit Number 99090252
Review Stop P
Sequence Number 9
Notes
Date Text
2001-01-08 00:00:001)SUBMIT DETAILED FLOOR PLAN OF TOILET
 ROOM ON FIRST FLOOR.TOILET ROOM SHALL
 COMPLY W/FACBC FOR ALL HANDICAP REQS.
 SHOW LOCATION OF REQD.DRINKING FOUNTAIN.
 FOUNTAIN SHALL COMPLY W/FACBC SEC.
 4.1.3(10)(A).PROVISIONS SHALL BE MADE
 FOR PEOPLE WHO HAVE TROUBLE BENDING AND
 STOOPING.
  
 2)SHT.P202-CLARIFY "HWC"IN TOILET ROOM.
  
 3)SHT.P206-A DRAIN IS REQD.ON THE WATER
 HEATER PAN.TERMINATION OF DRAIN SHALL
 COMPLY W/SPC SEC.507.8.3.DRAIN SHALL BE
 A MIN.OF 1".
  
 4)SHT.P207-RISER #3-SHOW SQ.FT.AREA
 DRAINED BY EACH CANOPY DRAIN.COMPLY W/
 SPC SEC.1108.1 AND TABLE 1108.1.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
  
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER.