8 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)SUBMIT DETAILED FLOOR PLAN OF TOILET | | ROOM ON 1ST.LEVEL AND LOCATION OF DRINK- | | ING FOUNTAIN.TOILET ROOM SHALL COMPLY W/ | | FACBC FOR ALL HANDICAP REQS.DRINKING | | FOUNTAIN SHALL COMPLY W/FACBC SEC. | | 4.1.3.(10) (A).(PROVISIONS SHALL BE MADE | | FOR PEOPLE WHO HAVE TROUBLE BENDING OR | | STOOPING.) | | | | 2)SHT.P206-HEATER PAN DRAIN CANNOT BE | | INSTALLED AS DRAWN.COMPLY W/COUNTYWIDE | | AMENDMENTS TO SPC SEC.507.8.4.ALSO,SEE | | NOTE ON SHT.P201. | | | | 3)SHT.P208-IF CONDENSATE MATERIAL ON | | ROOF IS PVC IT SHALL BE PAINTED W/A | | WATER BASED PAINT PER MANUF.RECOMMEND- | | ATIONS AND SUPPORTED AT MAX.4' INTERVALS | | NOT 6' AS NOTED.SPC SEC.310.3.6. | | | | CALL IF YOU HAVE ANY QUESTIONS | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|