2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SHOW ALL AIC RATINGS FOR
 ALL EQUIPMENT BEING SHOWN. ALL MAINS/
 PANELS/BREAKERS MUST BE RATED FOR
 AVAILABLE FAULT CURRENT. PER 110-9
 PLEASE SUBMIT ALL THE ABOVE PER 215-5
  
 2)NOTE: PLEASE NOTE THAT NOT ALL PANEL
 SCHEDULES WERE SHOWN?? PLEASE DO SO.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561-659-8096 EXT 8372