Plan Review Notes
Plan Review Notes For Permit 99090252
Permit Number 99090252
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00SUBMIT TOTAL OCCUPANT LOAD OF STRUCTURE
 PER SPC SEC.407.1.3.
  
 CONFIGURATION OF WOMEN'S RESTROOM ON SHT
 A1.5.DOESN'T CORRELATE W/SHTS.A1.2 OR
 A6.2.CLARIFY.
  
 CLEARLY SHOW LENGTH AND WIDTH DIMENSIONS
 OF HANDICAP STALLS AND TOILET ROOMS.
 COMPLY W/FACBC SEC.4.17.3 EXCEPTION:NEW
 CONSTRUCTION AND FIGURES 28 AND 30.
  
 GRAB BARS BEHIND WATER CLOSETS SHALL
 COMPLY W/FACBC SEC.4.16.4 & 4.17.6.
  
 CLEAR FLOOR SPACE UNDER HANDICAP LAVS.
 SHALL COMPLY W/FACBC SEC.4.19.2.
  
 SHOW MOUNTING HEIGHTS/DIMENSIONS OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/ALL APPLICABLE SECTIONS OF
 FACBC.
  
 DRINKING FOUNTAIN BY SECURITY OFFICE
 SHALL COMPLY W/FACBC SEC.4.1.3(10)(A)
  
 SUBMIT ISOMETRIC DRAWING FOR COMPLETE
 UNDERGROUND STORM DRAINAGE PIPING FOR
 THE BUILDING STORM DRAINAGE SYSTEM PER
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
 SIZING OF SYSTEM SHALL COMPLY W/SPC SEC.
 1108.2.1.SYSTEM DOESN'T COMPLY.
  
 SUBMIT CALCULATIONS/DETAILS FOR
 PROVISIONS FOR SECONDARY DRAINAGE FOR
 ROOF STRUCTURE PER SPC SEC.1109.SUBMIT
 DETAILS OF SCUPPERS W/ALL DIMENSIONS.
  
 CLEARLY SHOW TERMINATION POINT OF STORM
 DRAINAGE SYSTEM.(SEE 8"RISERS AND CANOPY
 AT ROTUNDA ON A200.)
  
 SHT.P200-RISER #4 -4"ROOF DRAIN NOT
 SHOWN ON SHT.P206.
  
 SHT.P201-RISER FOR MSB ON 2ND FLR.DOES
 NOT CORRELATE W/ISOMETRIC ON P206.(SEE
 AREA AT COLS.9-10 BETWEEN E-F.)
  
 FLOOR DRAINS IN RESTROOMS AND FAMILY
 TOILET ROOM ARE S-TRAPPED.COMPLY W/SPC
 SEC.901.2.
  
 SHOW SIZE OF CONDENSATE DRAINS ON PLANS.
 COMPLY W/SMC SEC.304.8.4.
  
 SHT.P206.-2ND.FLR.MEN'S AND WOMEN'S R.R.
 SIZING OF DRAINAGE SYSTEM SHALL COMPLY
 W/SPC TABLE 714.2.(REFER TO 1 1/2"& 2"
 DRAINS).
  
 BRANCH VENT SIZING FOR WATER CLOSETS
 SHALL COMPLY W/SPC TABLE 902.2.
  
 SHT.P206-JANITOR SINK NOT SHOWN ON WATER
 AND SANITARY RISERS.
  
 SHT.P201 REFERS TO SHT.P700 FOR CONTIN-
 UATION OF SANITARY.NO SUCH SHEET IS IN
 PLANS.
  
 A HEATER PAN AND PAN DRAIN ARE REQUIRED
 FOR THE EWH.COMPLY W/COUNTYWIDE AMEND-
 MENTS TO SPC SEC.507.8.1.
  
 MAX.TEMPERATURE OF WATER TO PUBLIC REST-
 ROOMS SHALL BE 110 DEGREES PER FEC SEC.
 412.1.ABCD.2.3.2.
  
 HOSE BIBBS SHALL BE VALVED PER SPC SEC.
 610.4.1.
  
 SHT.P206-WATER SUPPLY CONTROL SHALL
 COMPLY W/SPC SEC.610.4.1 & 610.4.2.
  
 VENTS THRU ROOF SHALL NOT BE INCREASED
 IN SIZE (ONLY WHERE FROST CLOSURE IS A
 PROBLEM.)SPC SEC.905.2,918,920.2.-SEE
 FUTURE RESTROOM AREA,& F.D.AT PUMP ROOM.
  
 THE FOLLOWING JOB SPECS.DO NOT COMPLY
 W/SPC.THEY SHALL BE CHANGED TO COMPLY
 W/THE FOLLOWING CODE SECS.:
 PAGE 15410-15-(H)(I)-VERT.AND HORIZONTAL
 SUPPORTS SHALL COMPLY W/SPC SEC.310.2-
 310.3.6.
 PAGE 15430-6-(3.3)-CLEANOUTS SHALL
 COMPLY W/SPC 710.2.4.
 PAGE 15497(1-3)SECS.3.2-3.5-SYSTEM TESTS
 SHALL COMPLY W/SPC SECS.311.2-311.7.5.