Date Text
2001-01-08 00:00:00********CORRECTED BY LETTER ATTACHED****
 EXHAUST FANS ARE NOT ALL INDICATED ON
 ROOF PROVIDE LOCATION FOR EACH FAN.
 PROVIDE AIR BALANCE SCHEDULE PER 1997
 SMC 501.2
 PROVIDE OUTSIDE AIT CALCULATIONS PER
 ASHRAE 62-89
 EXHAUST AIR TOTALS IN BUILDING DOES NOT
 MATCH FAN CAPACITY ON SCHEDULE