Plan Review Notes
Plan Review Notes For Permit 99090252
Permit Number 99090252
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT OCCUPANT LOAD PER SPC SEC.407.1.3
  
 NUMBER OF DRINKING FOUNTAINS FOR
 OCCUPANT LOAD SHALL COMPLY W/TABLE 407
 OF SPC.
  
 SUBMIT STORM DRAINAGE ISOMETRIC FOR
 REVIEW.COMPLY W/SPC SECS.1108.
  
 SUBMIT CALCULATIONS/DETAILS FOR
 PROVISIONS FOR SECONDARY DRAINAGE FOR
 ROOF STRUCTURE PER SPC SEC.1109.
  
 CONFIGURATION OF WOMEN'S RESTROOM ON
 A1.2 DOESN'T CORRELATE W/SHT.A1.5 OR
 A6.2.(AMOUNT OF PLBG.FIXTURES DOESN'T
 MATCH.)
  
 CLEARLY SHOW LENGTH AND WIDTH DIMENSIONS
 OF HANDICAP STALLS AND TOILET ROOM.
 COMPLY W/FACBC SEC.4.17.3 EXCEPTION:NEW
 CONSTRUCTION AND FIGURES 28 & 30.
  
 SHT.A6.2-GRAB BARS BEHIND WATER CLOSETS
 SHALL COMPLY W/FACBC SEC.4.16.4 & 4.17.6
  
 CLEAR FLOOR SPACE UNDER HANDICAP LAV.
 SHALL COMPLY W/FACBC SEC.4.19.2.
  
 SHOW MOUNTING HEIGHTS/DIMENSIONS OF ALL
 HANDICAP FIXTURES AND APPURTENANCES.
 COMPLY W/FACBC.
  
 DISTANCE OF FLOOR DRAINS FROM VENT SHALL
 COMPLY W/TABLE 908.1 OF COUNTYWIDE
 AMENDMENTS TO STD.PLBG.CODE.
  
 SHT.P200-CLEARLY SHOW CONTINUATION POINT
 OF 8" STORM DRAIN AND SANITARY LINE.SEE
 COLS.#B-D & "10".
  
 SUBMIT A STORM DRAINAGE ISOMETRIC FOR
 REVIEW.NOTE SQUARE FOOTAGE DRAINED BY
 EACH ROOF DRAIN.COMPLY W/SPC SEC.1108.1,
 1108.2.
  
 SHT.P201-RISER FOR MSB ON 2ND FLR.
 DOESN'T CORRELATE W/ISOMETRIC ON P206.
 SPC 104.2.1.
  
 FLOOR DRAINS ARE NOT PROPERLY VENTED PER
 SPC SEC.901.2
  
 FLOOR DRAIN IS REQD.IN THE FAMILY TOILET
 ROOM PER SPC SEC.409.4.1.1.
  
 SHT.P206-CLEARLY SHOW ORIGINATION POINT
 OF DOMESTIC WATER LINE.SPC 104.2.1.
 A BACKFLOW DEVICE IS REQD.ON THE WATER
 SERVICE TO THE BLDG.PER SPC SEC.606.
  
 JOB SPECS.-PG.15410-15.-(H)(I)-VERTICAL
 AND HORIZ.SUPPORTS SHALL COMPLY W/SPC
 SEC.310.2-310.3.6.
  
 JOB SPECS.-PG.15430-6.-(3.3)-CLEANOUTS
 SHALL COMPLY W/SPC 710.2.4.
  
 JOB SPECS.-PG.15497-SECS.3.2-3.5.SYSTEM
 TESTS SHALL COMPLY W/SPC SECS.311.2 -
 311.7.5.
  
 *************SHELL ONLY*****************
  
 SUBMIT ISOMETRIC DRAWINGS FOR ALL WATER,
 SANITARY,STORM AND CONDENSATE SYSTEMS TO
 BE INSTALLED IN THE SHELL STRUCTURE. .
 SPC 104.2.1.
  
 ROOF SYSTEM SHALL BE SUPPLIED W/
 PROVISIONS FOR SECONDARY DRAINAGE PER
 SPC SEC.1109.
  
 CLEARLY SHOW ORIGINATION /TERMINATION
 POINTS OF THE SANITARY,STORM,CONDENSATE,
 AND WATER SYSTEMS ON THE PLANS.SPC 104.2
  
 A BACKFLOW PREVENTION DEVICE IS REQD.ON
 THE DOMESTIC WATER SYSTEM PER SPC SEC.
 606.
  
 NOTE:PLUMBING PROVISO:
 THE ABOVE INFORMATION FOR THE SHELL BLDG
 SHALL BE SUBMITTED FOR REVIEW WITHIN
 30 DAYS OF ISSUANCE OF SHELL PERMIT.
 10/4/99.T.LARGE.