2001-01-08 00:00:00 | PREVIOUS COMMENTS DATED | | 3/5/00. | | | | SHT.M-4-DETAIL #4-SUPPLY AIR GAP ON | | CONDENSATE DRAIN PER SPC SEC.806. | | | | SUBMIT INFO ON PURITAN CHEMICAL STATIONS | | AS NOTED ON PLANS.COUNTYWIDE AMENDMENTS | | TO SPC SEC.104.2.1. | | | | EYEWASH DRAIN CANNOT DISCHARGE INTO | | FLOOR DRAIN IN TMA TOILET ROOM PER SPC | | SEC.807.1.1. | | | | RELIEF LINES FROM WATER HEATERS SHALL | | DISCHARGE TO EXTERIOR PER COUNTYWIDE | | AMENDMENTS TO SPC SEC.507.6.SEE SHT.P-3, | | DETAIL #3 ALSO. | | | | SUMP DISCHARGE PIPING SHALL CONNECT TO | | SANITARY SYSTEM PER SPC SEC.717.11. | | (SUMPS AND ASSOCIATED PIPING SHALL | | COMPLY W/SPC SEC.717.1-717.11. | | | | SUMP PIPING CONNECTION FROM VISION AND | | PHOTO AREAS TO SNACK BAR PIPING NOT | | SHOWN ONPLANS.COUNTYWIDE AMENDMENTS TO | | SPC SEC.104.2.1. | | | | SINKS AT VISION CENTER SHALL BE PROPERLY | | VENTED PER SPC SEC.901.2. | | | | GREASE RECOVERY UNITS NOT PERMITTED PER | | CITY OF WPB ORDINANCE. | | | | SHT.P-4-DETAIL#8-DRAINS CANNOT BE | | REDUCED IN SIZE PER SPC SEC.709.1. |
|