Plan Review Notes For Permit 99090218 |
Permit Number |
99090218 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** PROVISO *************** | | | | 1)NOTE: PLEASE REVISE SMOKE DETECTOR | | LOCATIONS. MUST BE INSIDE AND OUTSIDE | | ALL SLEEPING ROOMS AND ON EACH LEVEL | | OF MULTI-LEVEL DWELLING. NFPA-72 | | | | 2)NOTE: PLEASE LIST THE REQ`D DEDICATED | | BATH(S) CIRCUIT(S) ON PANEL SCHEDULE. | | AS PER 210-11-C-3/215-5 MUST BE 20AMP | | AND #12 AWG. | | | | PLEASE REVISE PLANS AND ANY AS-BUILTS | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. IF THERE ARE | | ANY QUESTIONS PLEASE CALL 659-8096 X8372 |
|