2001-01-08 00:00:00 | REVISION: |
| ROYAL WALL SYSTEM INSTEAD OF MASONRY: |
| |
| CHECKLIST: |
| 1-ROYAL WALL SYSTEM PRODUCT APPROVAL IS |
| APPROVED FOR PANELS UP TO 15'6" HIGH. |
| ENTRY TOWER IS 20'-8". PROVIDE A |
| COMPLETE SITE SPECIFIC ENGINEERING |
| ANALYSIS WITH COMPLETE CALCULATIONS, |
| SPECIFICATIONS AND DETAILS. |
| 2-FIRE RATED WALL DOESN'T MEET THE |
| REQUIREMENTS FOR SECTIONS 709.2.1.4.4 |
| AND 709.2.1.4.5 SBC 1997. |
| CALCULATIONS ARE INCORRECT. |
| 3-WHEN WALL FINISHES CONTRIBUTE TO GET |
| THE TOTAL FIRE RESISTANCE OF THE WALL, |
| THEN, THEY SHALL BE INSTALLED AS PER |
| SECTION 709.3.1.6 SBC 1997. PROVIDE |
| SUCH SPECIFICATIONS. |
| 4-PROVIDE COMPLETE DETAILS AND SPECS FOR |
| CONCRETE PANELS WITH ROUND AND ARCHED |
| OPENINGS. SECTION 104.2.2 CITY |
| AMENDMENTS TO SBC 1997. |
| 5-PROVIDE INFORMATION SHOWING THE R |
| VALUE (12.9) CALCULATED IN THE ENERGY |
| CALCULATIONS. SEC 104.2.2 AMENDMENTS. |
| 6-PROVIDE COPIES OF APPROVED DRAWINGS |
| REFERENCED IN THE PRODUCT APPROVAL. |
| 7-REVISE THE DESIGN CERTIFICATION FOR |
| BUILDING CODE COMPLIANCE FORM. THE |
| MEAN ROOF HEIGHT IS 23'-6" MORE OR |
| LESS. |
| |
| FROM PREVIOUS PROVISO: |
| 1-STORM PANELS: |
| -PROVIDE A COMPLETE INSTALLATION |
| SCHEDULE AS PER CITY SAMPLE. |
| -PROVIDE DETAIL FOR INSTALLATION OF |
| STORM PANEL AT FRONT WINDOW. SEE SILL |
| DETAIL. |
| 2-PROVIDE PRODUCT APPROVAL FOR ENTRY |
| DOORS, WINDOW AT DINING AREA AND |
| ARCHED WINDOW. |
| 3-UPDATE ALL ENGINEERED DRAWINGS. CUT |
| AND PASTE IS NOT ACCEPTABLE. |