2001-01-08 00:00:00REVISION:
 ROYAL WALL SYSTEM INSTEAD OF MASONRY:
  
 CHECKLIST:
 1-ROYAL WALL SYSTEM PRODUCT APPROVAL IS
 APPROVED FOR PANELS UP TO 15'6" HIGH.
 ENTRY TOWER IS 20'-8". PROVIDE A
 COMPLETE SITE SPECIFIC ENGINEERING
 ANALYSIS WITH COMPLETE CALCULATIONS,
 SPECIFICATIONS AND DETAILS.
 2-FIRE RATED WALL DOESN'T MEET THE
 REQUIREMENTS FOR SECTIONS 709.2.1.4.4
 AND 709.2.1.4.5 SBC 1997.
 CALCULATIONS ARE INCORRECT.
 3-WHEN WALL FINISHES CONTRIBUTE TO GET
 THE TOTAL FIRE RESISTANCE OF THE WALL,
 THEN, THEY SHALL BE INSTALLED AS PER
 SECTION 709.3.1.6 SBC 1997. PROVIDE
 SUCH SPECIFICATIONS.
 4-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONCRETE PANELS WITH ROUND AND ARCHED
 OPENINGS. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 5-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) CALCULATED IN THE ENERGY
 CALCULATIONS. SEC 104.2.2 AMENDMENTS.
 6-PROVIDE COPIES OF APPROVED DRAWINGS
 REFERENCED IN THE PRODUCT APPROVAL.
 7-REVISE THE DESIGN CERTIFICATION FOR
 BUILDING CODE COMPLIANCE FORM. THE
 MEAN ROOF HEIGHT IS 23'-6" MORE OR
 LESS.
  
 FROM PREVIOUS PROVISO:
 1-STORM PANELS:
 -PROVIDE A COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE.
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANEL AT FRONT WINDOW. SEE SILL
 DETAIL.
 2-PROVIDE PRODUCT APPROVAL FOR ENTRY
 DOORS, WINDOW AT DINING AREA AND
 ARCHED WINDOW.
 3-UPDATE ALL ENGINEERED DRAWINGS. CUT
 AND PASTE IS NOT ACCEPTABLE.