Plan Review Notes
Plan Review Notes For Permit 99090087
Permit Number 99090087
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00APPROVED WITH PROVISO:
 1-PLEASE REVISE ALL ORIGINAL DRAWINGS
 SHOWING ALL CORRECTIONS/CLARIFICATIONS
 AS REQUESTED ON PLANS.
 2-PROVIDE 32" MINIMUM CLEAR OPENING AT
 ENTRY DOOR. TABLE 1004 SBC 1997.
 3-REVISE DESIGN CERTIFICATION FOR WIND
 LOAD COMPLIANCE FORM. MEAN ROOF HEIGHT
 IS 23'-6" PLUS O MINUS. SEE COMMENTS
 ON PLANS.
 4-PROVIDE ATTIC ACCESSS AT ENTRY TOWER
 AND AT GUEST SUITE/GOLFCART AREA AS
 PER SEC. 2309.6 SBC 1997.
 5-PROVIDE SIZES OF CEILING FANS AS PER
 TABLE 6-6 OF FLORIDA ENERGY CODE, 1997
 6-CLARIFY IF FIXED WINDOW AT GRAND ROOM
 HAS TRUE MULLIONS OR NOT IN ORDER TO
 VERIFY ACTUAL SIZE OF WINDOW.
 7-STORM PANELS: PROVIDE A COMPLETE
 INSTALLATION SCHEDULE AS PER CITY
 SAMPLE AND KEY PLAN.
 8-PROVIDE TWO COPIES OF ENGINEERED ROOF
 TRUSSES SIGNED AND SEALED AND REVIEWED
 BY DESIGNER OF RECORD.
 9-PROVIDE PRODUCT APPROVAL FOR WINDOW AT
 DINING AREA.