2001-01-08 00:00:00*************PROVISO********************
  
 1)NOTE:NO EQUIPMENT GROUND FROM METER
 THE FIRST MEANS OF DISC.
 2)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO BLDG.STEEL ALSO.
 3)NOTE:PANEL SCHEDULE TO SHOW BATH
 CIRCUT.
 4)NOTE:AS PER ART;210-63 RECEPT.REQ`D
 FOR A/C COND.UNIT.
 5)NOTE:NEED TO HAVE AIC RATING LISTED ON
 PANELSCHED/RISER DIAGRAM AS PER ART;
 110-9, 215-5
  
  
 NEED TO SUBMIT THE ABOVE BEFORE THE
 FIRST ROUGH ELECTRICAL INSPECTION.