Plan Review Notes
Plan Review Notes For Permit 99090086
Permit Number 99090086
Review Stop R
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00REVISION: ROYAL WALL SYSTEM IN LIEU OF
 MASONRY CONSTRUCTION.
  
 CHECKLIST:
 1-FIRE RATED WALL AT ZERO LOT LINE DOES
 NOT MEET THE REQUIREMENTS FOR SECTION
 709.2.1.4.4 AND SECTION 709.2.1.4.5
 SBC 1997.(CALCS ARE INCORRECT).
 2-WHEN FINISHES ON CONCRETE WALLS ARE
 ASSUMED TO CONTRIBUTE TO THE TOTAL
 FIRE RESISTANCE OF THE WALL, THEN THE
 INSTALLATION REQUIREMENTS SHALL BE AS
 PER SECTION 709.3.1.6 SBC 1997.
 SECTION 709.2.1.4.6 SBC 1997.
 3-PROVIDE COMPLETE DETAILS AND SPECS FOR
 CONCRETE PANELS WITH ROUND AND ARCHED
 OPENINGS. SEC. 104.2.2 CITY AMENDMENTS
 4-PROVIDE INFORMATION SHOWING THE R
 VALUE (12.9) FOR THE INSULATION SHOWN.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 5-DETERMINE WHICH ROYAL WALL SYSTEM
 PRODUCT APPROVAL IS GOING TO BE USED.
 DADE COUNTY OR SBCCI. AND PROVIDE
 COPIES OF THE APPROVED DRAWINGS.
 6-PROVIDE COMPLETE DETAILS AND SPECS FOR
 COLUMN AT COVERED PORCH.
 SECTION 104.2.2 CITY AMENDMENTS.
  
 FROM PREVIOUS PROVISO, DATED 10/13/99:
 1-PROVIDE PRODUCT APPROVAL FOR:
 FIXED WINDOW AT LIVING AREA, ENTRY
 DOORS, ROUND AND ARCHED WINDOWS.
 2-STORM PANELS:
 -PROVIDE COMPLETE INSTALLATION
 SCHEDULE AS PER CITY SAMPLE (ATTACHED)
 -PROVIDE DETAIL FOR INSTALLATION OF
 STORM PANELS AT FRONT WINDOWS. SEE
 EXTERIOR SILL DETAIL AND INSTALLATION
 SCHEDULE.
 3-TRUSS DRAWINGS:
 -UPDATE ALL DETAILS AND ENGINEERED ROOF
 TRUSSES. ENGINEERED TRUSSES SHOW CUT
 AND PASTE INFORMATION SHOWING THE
 DESIGN CRITERIA TO BE SBC 1997.
 THIS IS NOT ACCEPTABLE.
 -CLARIFY/REVISE IF TRUSS FGT4 IS ONE
 PLY OR TWO PLYS.