Plan Review Notes
Plan Review Notes For Permit 99090086
Permit Number 99090086
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*****************PROVISO**************
  
 1)NOTE: NEED TO SUBMIT AIC RATING OF
 ALL EQUIPMENT AND MAINS AS PER ARTS;
 110-9/215-5 FIGURED FROM FAULT CURRENT
 CALCULATIONS.
 2)NOTE; EQUIPMENT GROUNDING CONDUCTOR IS
 ONLY TO BE INSTALLED AFTER FIRST MEANS
 OF DISC.
 3)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR IS REQ`D TO GO TO
 BLDG.STEEL ALSO.
 4)NOTE: AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 5)NOTE:MASTER BEDROOM HALLWAY AS PER ART
 210-52H
  
 NEED TO SUBMIT ALL THE ABOVE INFORMATION
 FOR APPROVAL BEFORE FIRST ELECTRICAL
 INSPECTION.