Plan Review Notes For Permit 99090086 |
Permit Number |
99090086 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *****************PROVISO************** | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | ALL EQUIPMENT AND MAINS AS PER ARTS; | | 110-9/215-5 FIGURED FROM FAULT CURRENT | | CALCULATIONS. | | 2)NOTE; EQUIPMENT GROUNDING CONDUCTOR IS | | ONLY TO BE INSTALLED AFTER FIRST MEANS | | OF DISC. | | 3)NOTE:AS PER ART;250-81 GROUNDING | | ELECTRODE CONDUCTOR IS REQ`D TO GO TO | | BLDG.STEEL ALSO. | | 4)NOTE: AS PER ART;210-8-A-6 ALL OUTLETS | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. | | 5)NOTE:MASTER BEDROOM HALLWAY AS PER ART | | 210-52H | | | | NEED TO SUBMIT ALL THE ABOVE INFORMATION | | FOR APPROVAL BEFORE FIRST ELECTRICAL | | INSPECTION. |
|