Plan Review Notes For Permit 99090050 |
Permit Number |
99090050 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | WATER CLOSETS,SHOWERS AND TUBS ON 2ND.FL | | ARE NOT PROPERLY VENTED.COMPLY W/SPC | | SEC.901.2 | | | | 2ND.FLR.PLUMBING CANNOT DRAIN INTO VENT | | FOR 1ST.FLR.FIXTURES.SPC.SEC.904.1. | | | | MAX.2 WATER CLOSETS PERMITTED ON 3" | | BUILDING DRAIN PER SPC TABLE 714.1 | | FOOTNOTE #3. | | | | ONLY FIXTURE DRAINS PERMITTED ON HORIZ. | | WET VENTS PER COUNTYWIDE AMENDMENTS TO | | SPC SEC.911.1.1. |
|