Plan Review Notes For Permit 99090050
Permit Number 99090050
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00WATER CLOSETS,SHOWERS AND TUBS ON 2ND.FL
 ARE NOT PROPERLY VENTED.COMPLY W/SPC
 SEC.901.2
  
 2ND.FLR.PLUMBING CANNOT DRAIN INTO VENT
 FOR 1ST.FLR.FIXTURES.SPC.SEC.904.1.
  
 MAX.2 WATER CLOSETS PERMITTED ON 3"
 BUILDING DRAIN PER SPC TABLE 714.1
 FOOTNOTE #3.
  
 ONLY FIXTURE DRAINS PERMITTED ON HORIZ.
 WET VENTS PER COUNTYWIDE AMENDMENTS TO
 SPC SEC.911.1.1.