Plan Review Notes For Permit 99090050 |
Permit Number |
99090050 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************UNSAT******************** | | | | 1)NOTE:NEED TO SHOW LOCATION OF PROPOSED | | PANEL'B' ART;215-5 | | 2)NOTE;NEED TO SHOW ON PANEL SCHED. AND | | LOAD CALCULATIONS TWO SMALL PER KITCHEN. | | ART;215-5 | | 3)NOTE;BATH CIRCUT/S ARE NOT SHOWN ON | | PANEL 'A' AND REQ`S DEDICATED CIRCUT | | AS PER ART;210-52D | | 4)NOTE;QUESTION AS TO 6-2/0 CONDUCTORS | | TO PANEL 'A'??? | | 5)NOTE;IF PROPOSED PANEL'B' IS TO FEED | | SEPARATE BLDG. THEN MAINS MUST BE | | GROUPED AS PER ART; 230-72 | | 6)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS. | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | GFI/GFI PROTECTED. | | 7)NOTE;AS PER ART;210-52E WP GFI RECEPTS | | ARE REQ`D FRONT AND BACK OF DWELLINGS. | | 8)NOTE;AS PER ART;210-63 A RECEPT. IS | | REQ`D FOR THE A/C COND. UNIT. | | 9)NOTE; PLEASE SHOW DISC.S FOR A/C COND. | | UNITS AS PER ART;440-11 | | 10)NOTE;POWDER ROOM BY FRONT DOOR REQ`S | | GFI RECEPT. AND TO BE ON BATH CIRCUT. | | AS PER ART;210-52D | | 11)NOTE;RECEPT.AND LIGHT REQ`D FOR AHU | | IN ATTIC.210-70/210-63 | | 12)NOTE;THERE ARE NUMEROUS LOCATIONS | | FOR OUTLETS REQ`D BY ART;210-52 | | NOTE THE 2`6`12` RULE. | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | AND RESUBMIT. |
|