2001-01-08 00:00:00***************PROVISO*****************
  
 1)NOTE:SUBMIT AIC RATING FIGURED FROM
 FAULT CURRENT CALCULATIONS,ART;110-9/
 215-5
 2)NOTE:AS PER ART;250-81 GROUNDING
 ELECTRODE CONDUCTOR TO GOT TO BLDG.STEEL
 ALSO.
 3)NOTE:AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE.
 4) NOTE;AS PER ART;210-52 NOTE 2`6`12
 RULE FOR OUTLET SPACING.
 5)NOTE;AS PER 1996 NFPA-72
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE ALL SLEEPING ROOMS IN NEW
 CONTRUCTION OF DWELLING UNITS.
 NEED TO HAVE THE ABOVE SUBMITTED AND
 APPROVED BEFORE ROUGH ELECTRICAL
 INSPECTION.