Plan Review Notes For Permit 99081314 |
Permit Number |
99081314 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT SANITARY ISOMETRICS FOR PLBG.WORK | | TO BE DONE IN EACH STRUCTURE.SPC SEC. | | 104.2.1. | | | | FIXTURES LOCATED DOWNSTREAM OF WATER | | CLOSETS SHALL BE VENTED PER SPC SEC. | | 913.2 | | | | WASHING MACHINE NOT PERMITTED ON 2"CROSS | | PER SPC SEC.409.12.3. | | | | VEGGIE SINK,BAR SINK,AND 2ND FLR.LAV.ARE | | SHOWN ON THE FLOOR PLAN BUT NOT ON THE | | SANITARY ISOMETRIC.SPC 104.2.1. | | | | SHOW FIXTURE CLEARANCES OF WATER CLOSETS | | COMPLY W/SPC SEC.403.4. | | | | WATER CLOSET AND SHOWER ARE NOT PROPERLY | | VENTED.COMPLY W/SPC SEC.901.2.(SEE TUB | | AND SHOWER ON 2ND.FLR.ALSO.) | | | | SANITARY ISOMETRIC SHALL CORRELATE W/ | | THE FLOOR PLAN.SPC 104.2.1. | | | | DIMENSIONS REQD.FOR GARAGE SHOWER.COMPLY | | W/COUNTYWIDE AMENDMENTS SEC.409.8.2.1. |
|