2001-01-08 00:00:00************DENIED**********************
  
 1)NOTE:SERVICE ENTRANCE CONDUCTORS NEED
 TO BE SIZED FOR ATLEAST THE LOAD OF THE
 SERVICE!!!!!!
 2)NOTE:PLEASE REVISE LOAD CALCULATION
 COMBINING BOTH PANELS FOR SERVICE
 CALCULATION.
 3)NOTE:RISER ONLY SHOWS 4/0 WHICH IS
 RATED FOR 230 AMPS AND CAN BE PROTECTED
 AT 250A BUT THE LOAD EXCEEDS THAT RATING
 OF THE WIRE.AS PER 310-16!!!!!
 SIZE SERVICE ENTRANCE CONDUCTORS ACCORD.
 4)NOTE:PLANS SHOW 2 WATER HEATERS AND
 2 DRYERS???? PANEL SCHEDULES AND LOAD
 CALCULATIONS ONLY SHOW ONE OF EACH
 BEING FIGURED???? PLEASE VERIFY!!!
 5)NOTE: PLEASE ADD CIRCUT(S) ON PANEL
 SCHD.THAT ARE REQ`D BY 210-52D FOR BATHS
 6)NOTE:NEED TO HAVE GROUNDING ELECTRODE
 CONDUCTOR GOING TO STEEL OF NEW
 STRUCTURES.AS PER 250-81
 7)NOTE:AT DETACHED STRUCTURE BACK YARD,,
 IF FED BY MORE THAN ONE BRANCH CIRCUT
 THEN MUST MEET CODE AS TO PROPER GROUND-
 -ING. AS PER 250-24 C-3
 8)NOTE:ON PLANS,,,SHEET 5 OF 15 SHOW
 4 A/C COND. UNITS AND 9 OF 15 SHOW ONLY
 2 A/C COND. UNITS??? ALSO PLANS 3 AHU`S
 ??WHAT ARE THE CORRECT AMOUNT OF UNITS??
 9)NOTE:AS REQ`D BY ART;210-8-A-6 ALL
 OUTLETS SERVING KITCHEN COUNTERSPACE ARE
 TO BE GFI/GFI PROTECTED. PLEASE LABEL.
 10)NOTE:PLEASE NOTE SOME MISSING OUTLETS
 THAT ARE REQ`D BY 210-52
 11)NOTE:NEED TO SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS AND BRKRS.AIC RATING IS
 IGURED FROM FAULT CURRENT CALCULATIONS.
 AS REQ`D BY 110-9/10 AND 215-5
 NOTE ALL THE ABOVE SERVICE INFORMATION
 REQ`D BY 215-5
  
 PLEASE SUBMIT ALL THE ABOVE INFORNATION
 REQ`STED FOR REVIEW AND APPROVAL!!
 ELEC WILL NOT PRINT