Plan Review Notes
Plan Review Notes For Permit 99081314
Permit Number 99081314
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00****************DENIED******************
  
 1)NOTE:AS PER ART210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED, TO INCLUDE KITCHEN
 AREA.
 2)NOTE;IF DETACHED CABANA HAS NORE THAN
 ONE CIRCUT TO THAT STUCTURE,THEN IT REQ`
 S A MEANS OF DISC. ST THAT STRUCTURE.
 3)AS PER 310-16 SERVICE ENTRANCE CONDS.
 ARE NOT OF SUFFICENT SIZE.LOAD CALCS.
 SHOW LOAD ON PANEL'A' AT 186.22 AND LOAD
 ON PANEL'B'AT 80.54 THATS 266.76 ON 4/0
 WIRE WHICH IS ONLY RATED FOR 230AMPS!!!
 SIZE CONDUCTORS AS PER 310-16 TO GUTTER
 TAPS MAY BE SIZED TO PANEL RATING.
 4)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 SUBMIT AIC RATING OF ALL EQUIPMENT
 BEING USED TO INCLUDE AIC RATING OF
 MAINS,
 5)NOTE;SIZE GUTTER TO NEW SERVICE
 CONDUCTORS
 6)NOTE;SIZE GROUNDING ELECTRODE COND-
 -UCTOR TO NEW SERVICE ENTRANCE CONDUCTOR
 7)NOTE;AS PER ART 250-81,GROUNDING ELEC-
 -TRODE CONDUCTOR TO GOT TO TO BLDG.
 STEEL OF NEW ADDITIONS.
  
 NEED TO SUBMIT THE ABOVE INFORMATION
 FOR APPROVAL.