Plan Review Notes
Plan Review Notes For Permit 99081124
Permit Number 99081124
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00#47 PLUMBING PLAN REVIEW
 UNSAT PHASE III
 (1A) SHT A-2 MINIMUM FACILITIES TAB 407
 OFFICE SPACE OVER 1200 SQ FT REQUIRES
 REST RM'S FOR MEN & WOMEN,SEPERATE.
 (B)WHEEL CHAIR TURNING SPACE,
 FACBC 4.2.3 FIG 28.
 (C) GRAB BARS FACBC 4.26.
 (D) DRINKING FOUNTAIN REQ.TAB 407,TO
 COMPLY WITH FACBC 4.1.3 (10) (A).
 (E) URNIALS & WATER CLOSETS,SEC.404.3
 PRIVACY SCREEN REQUIRED.
 (2) SHT A-6 ROOF DRAINS & SCUPPERS
 SEC 1109 SECONDARY SYSTEM REQUIRED.
 (3) BACK FLOW PREVENTER ON WATER SERVICE
 REQUIRED SEC 606.
 (4) WATER PIPING ISOMETRIC SHOW LOCATION
 OF BACK FLOW PREVENTER & WATER HEATER.
 END OF COMMENTS