Plan Review Notes For Permit 99081098 |
Permit Number |
99081098 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PLANS SHALL BE SIGNED AND SEALED BY A | | ESIGN PROFESSIONAL PER SPC SEC.104.2.3. | | | | SUBMIT A WATER RISER DIGRAM FOR REVIEW. | | WATER SUPPLY CONTROL SHALL COMPLY W/SPC | | SEC.610.4.1.,610.4.2. | | | | FLOOR DRAINS ARE REQ'D. IN THE TOILET | | ROOMS PER SPC SEC.409.4.1.1. | | | | FLOORS AND WALLS SHALL BE NONABSORBENT | | MATERIAL TO A HEIGHT OF 4' PER SBC | | 1204.2. | | | | TOILET ROOMS SHALL COMPLY W/FACBC IN | | ALL RESPECTS FOR HANDICAP ACCESSIBILITY. | | SUBMIT ELEVATION DETAILS FOR ALL HANDI- | | CAP FIXTURES. | | | | PIPES EMBEDDED IN CONCRETE SHALL COMPLY | | W/SBC SEC.1907.3.5,1907.3.6. |
|