Plan Review Notes
Plan Review Notes For Permit 99081098
Permit Number 99081098
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PLANS SHALL BE SIGNED AND SEALED BY A
 ESIGN PROFESSIONAL PER SPC SEC.104.2.3.
  
 SUBMIT A WATER RISER DIGRAM FOR REVIEW.
 WATER SUPPLY CONTROL SHALL COMPLY W/SPC
 SEC.610.4.1.,610.4.2.
  
 FLOOR DRAINS ARE REQ'D. IN THE TOILET
 ROOMS PER SPC SEC.409.4.1.1.
  
 FLOORS AND WALLS SHALL BE NONABSORBENT
 MATERIAL TO A HEIGHT OF 4' PER SBC
 1204.2.
  
 TOILET ROOMS SHALL COMPLY W/FACBC IN
 ALL RESPECTS FOR HANDICAP ACCESSIBILITY.
 SUBMIT ELEVATION DETAILS FOR ALL HANDI-
 CAP FIXTURES.
  
 PIPES EMBEDDED IN CONCRETE SHALL COMPLY
 W/SBC SEC.1907.3.5,1907.3.6.