Plan Review Notes For Permit 99081016 |
Permit Number |
99081016 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************PROVISO****************** | | | | 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO | | HAVE AIC RATING DRAWN ON PANEL SCEDULE | | FIGURED FROM FAULT CURRENT CALCULATIONS | | 2)NOTE:AS PER ART;250-81 NEED TO SHOW | | GROUNDING ELECTRODE CONDUCTOR GOING TO | | COLD WATER PIPE AND BLDG.STEEL ALSO. | | 3)NOTE:RISER DIAGRAM SHOWS MAIN LUG ONLY | | (MLO) PANEL ,YET PANEL SCHED.SHOWS | | MAIN CIRCUT BRKR.(MCB) PLEASE MATCH | | BOTH. A MAIN BRKR. OR MAIN DISC. IS | | REQ`D. | | | | NEED TO HAVE SUBMITTED FOR REVIEW AND | | APPROVAL BEFORE FIRST ROUGH ELECTRICAL | | INSPECTION. |
|