2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:AS PER ARTS;110-9/215-5 NEED TO
 HAVE AIC RATING DRAWN ON PANEL SCEDULE
 FIGURED FROM FAULT CURRENT CALCULATIONS
 2)NOTE:AS PER ART;250-81 NEED TO SHOW
 GROUNDING ELECTRODE CONDUCTOR GOING TO
 COLD WATER PIPE AND BLDG.STEEL ALSO.
 3)NOTE:RISER DIAGRAM SHOWS MAIN LUG ONLY
 (MLO) PANEL ,YET PANEL SCHED.SHOWS
 MAIN CIRCUT BRKR.(MCB) PLEASE MATCH
 BOTH. A MAIN BRKR. OR MAIN DISC. IS
 REQ`D.
  
 NEED TO HAVE SUBMITTED FOR REVIEW AND
 APPROVAL BEFORE FIRST ROUGH ELECTRICAL
 INSPECTION.