Plan Review Notes For Permit 99080943 |
Permit Number |
99080943 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT DETAIL OF REINFORCEMENT OF WALLS | | FOR FUTURE INSTALLATION OF GRAB BARS AS | | REQUIRED BY FEDERAL FAIR HOUSING ACT | | 24 CFR 100.205 SEC.3 REQUIREMENT#6. | | NOTE:ALL BATHROOMS WITHIN THE COVERED | | DWELLING UNIT SHALL COMPLY. | | | | ALL BATHROMS IN THE DWELLING UNIT SHALL | | COMPLY W/THE PROVISIONS OF FEDERAL FAIR | | HOUSING ACT 24 CFR 100.205 (C)(3)(IV) | | REQ.#7 (2) PARAGRAPH (A) OR (B).CLEAR | | FLOOR SPACE SHALL BE PROVIDED AT | | FIXTURES TO ALLOW A PERSON IN A WHEEL- | | CHAIR OR OTHER MOBILITY AID USE OF THE | | FIXTURES.CLEAR FLOOR SPACE SHALL BE | | SHOWN ON THE PLANS AND DESIGNATE WHICH | | OPTION OF REQUIREMENT #7 (A OR B) IS | | BEING USED. |
|