Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO**************** | | | | 1)NOTE: NEED TO SUBMIT AIC RATING OF | | EQUIPMENT AND BRKRS.AS PER ARTS;215-5/ | | 110-9 | | 2)NOTE:AS PER ART:210-8-A-6 ALL RECEPTS. | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. | | 3)NOTE:AS PER ART;250-81 GROUNDING | | ELECTRODE CONDUCTOR TO GOT TO BLDG. | | STEEL ALSO. | | 4)NOTE:AS PER 1996-NFPA-72 SMOKE | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | ALL SLEEPING ROOMS IN NEW CONSTRUCTION. | | | | NEED TO SUBMIT THE ABOVE INFORMATIONN | | FOR APPROVAL BEFORE THE FIRST ROUGH | | ELECTRICAL INSPECTION. |
|