Plan Review Notes
Plan Review Notes For Permit 99080455
Permit Number 99080455
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************PROVISO*********************
  
 1)NOTE: PLEASE SUBMIT AIC RATING OF
 EQUIPMENT AND BREAKERS. HAVE DRAWN ON
 ROSER DDIAGRAM.AS PER ARTS;215-5,110-9
 2)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 REQ`S SMOKE DETECTORS INSIDE AND
 OUTSIDE ALL BEDROOMS IN NEW CONSTRUCTION
  
 NEEDS TO BE SUBMITTED AND APPROVED
 BEFORE ROUGH ELECTRICAL INSPECTION.