2001-01-08 00:00:00**************PROVISO*******************
  
 1)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 2)AS PER ART;250-81 GROUNDING ELECTRODE
 CONDUCTOR TO BLDG.STEEL ALSO.
 3)NOTE;AS PER 210-52 NOTE MISSING RECEPT
 4)NOTE;AS PER 1996/1993 NFPA-72 SMOKE
 DETECTORS ARE REQ`D INSIDE AND OUTSIDE
 ALL SLEEPING ROOMS.
 5)NOTE;AS PER ARTS;110-9/215-5 PLEASE
 SUBMIT AIC RATING OF EQUIPMENT AND
 BREAKERS.AIC RATING IS FIGURED FROM
 FAULT CURRENT CALCULATIONS.
  
 THE ABOVE NEEDS TO BE SUBMITTED AND
 APPROVED BEFORE FIRST ELECTRICAL ROUGH
 INSPECTION.