Plan Review Notes For Permit 99080423 |
Permit Number |
99080423 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO******************* | | | | 1)NOTE;AS PER ART;210-8-A-6 ALL RECEPTS. | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | GFI/GFI PROTECTED. | | 2)AS PER ART;250-81 GROUNDING ELECTRODE | | CONDUCTOR TO BLDG.STEEL ALSO. | | 3)NOTE;AS PER 210-52 NOTE MISSING RECEPT | | 4)NOTE;AS PER 1996/1993 NFPA-72 SMOKE | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | ALL SLEEPING ROOMS. | | 5)NOTE;AS PER ARTS;110-9/215-5 PLEASE | | SUBMIT AIC RATING OF EQUIPMENT AND | | BREAKERS.AIC RATING IS FIGURED FROM | | FAULT CURRENT CALCULATIONS. | | | | THE ABOVE NEEDS TO BE SUBMITTED AND | | APPROVED BEFORE FIRST ELECTRICAL ROUGH | | INSPECTION. |
|