2001-01-08 00:00:00 | *************** UNSAT ****************** | | | | 1)NOTE: SAME AS FIRST SET OF NOTES. | | NEED TO SHOW WHAT YOUR POWER SOURCE IS | | ON THE THIRD FLOOR. YOU SAY INTERCEPTING | | AS REQ`D ???? NEED TO SHOW WHERE THE | | FEEDS ARE COMING FROM AND THE SIZE????" | | | | 2)NOTE: PLEASE SHOW ON LOAD CALCULATION | | THE LOADS THAT ARE CONTINUOUS(LIGHING) | | AND SHOW LOAD FIGURED AT 125%.ART 210-19 | | 384-16C | | | | PLEASE SUBMIT THE ABOVE INFORMATON FOR | | REVIEW. IF THERE ARE ANY QUESTIONS CALL | | 659-8096 EXT 8372 |
|