Plan Review Notes
Plan Review Notes For Permit 99080267
Permit Number 99080267
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00*****************PROVISO****************
  
 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSDIE AND
 OUTSIDE BEDROOMS IN NEW CONTRUCTION OF
 HOMES.
 2)NOTE:AS PER ART;210-8-A-6 ALL RECEPTS.
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 3) NOTE:MASTER BEDROOM WALL INSIDE DOOR
 REQ`S RECEPT.UNDER 210-52
 4) NOTE:NEED TO SUBMIT AIC RATING OF
 ALL EQUIPMENT, PANELS,DISC`S AND
 BREAKERS, AS PER ARTS 110-9 AND 215-5
 5) NOTE: GROUNDING ELECTRODE CONDUCTOR
 REQ`D TO GO TO GRND. ROD AND BLDG.STEEL
 AS PER ART 250-81
  
 NEED TO HAVE PLANS SUBMITTED AND
 APPROVED BEFORE ELECTRICAL ROUGH
 INSPECTION.