Plan Review Notes For Permit 99080267 |
Permit Number |
99080267 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *****************PROVISO**************** | | | | 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | SMOKE DETECTORS ARE REQ`D INSDIE AND | | OUTSIDE BEDROOMS IN NEW CONTRUCTION OF | | HOMES. | | 2)NOTE:AS PER ART;210-8-A-6 ALL RECEPTS. | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. | | 3) NOTE:MASTER BEDROOM WALL INSIDE DOOR | | REQ`S RECEPT.UNDER 210-52 | | 4) NOTE:NEED TO SUBMIT AIC RATING OF | | ALL EQUIPMENT, PANELS,DISC`S AND | | BREAKERS, AS PER ARTS 110-9 AND 215-5 | | 5) NOTE: GROUNDING ELECTRODE CONDUCTOR | | REQ`D TO GO TO GRND. ROD AND BLDG.STEEL | | AS PER ART 250-81 | | | | NEED TO HAVE PLANS SUBMITTED AND | | APPROVED BEFORE ELECTRICAL ROUGH | | INSPECTION. |
|