Plan Review Notes For Permit 99080265 |
Permit Number |
99080265 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************PROVISO****************** | | | | 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1 | | SMOKE DETECTORS ARE REQD INSIDE AND | | OUTSIDE BEDROOMS. | | 2)NOTE:GOUNDING ELECTRODE CONDUCTOR | | IS REQ`D TO GO TO GRND.ROD AND BLDG. | | STEEL ALSO AS PER 250-81 | | 3)NOTE:AS PER 210-8-A-6 ALL RECEPTS, | | SERVING KITCHEN COUNTER SPACE ARE TO BE | | GFI/GFI PROTECTED. | | 4)NOTE:PLEASE DRAW IN LOCATION OF SECOND | | A/C COND. UNIT, DISC, AND WP GFI AS REQ` | | D BY 210-63. | | PLEASE SUBMIT THE AIC RATING OF ALL | | EQUIPMENT AND BREAKERS BEING USED, FIG- | | IURED FROM FAULT CURRNET CACULATIONS. | | AS PER 110-9 AND 215. | | | | PLEASE SUBMIT AND HAVE APPROVED FOR | | APPROVAL BEFORE FIRST ELECTRICAL ROUGH | | INSPECTION, |
|