2001-01-08 00:00:00***************PROVISO******************
  
 1)NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQD INSIDE AND
 OUTSIDE BEDROOMS.
 2)NOTE:GOUNDING ELECTRODE CONDUCTOR
 IS REQ`D TO GO TO GRND.ROD AND BLDG.
 STEEL ALSO AS PER 250-81
 3)NOTE:AS PER 210-8-A-6 ALL RECEPTS,
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 4)NOTE:PLEASE DRAW IN LOCATION OF SECOND
 A/C COND. UNIT, DISC, AND WP GFI AS REQ`
 D BY 210-63.
 PLEASE SUBMIT THE AIC RATING OF ALL
 EQUIPMENT AND BREAKERS BEING USED, FIG-
 IURED FROM FAULT CURRNET CACULATIONS.
 AS PER 110-9 AND 215.
  
 PLEASE SUBMIT AND HAVE APPROVED FOR
 APPROVAL BEFORE FIRST ELECTRICAL ROUGH
 INSPECTION,