Plan Review Notes For Permit 99080263 |
Permit Number |
99080263 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************ PROVISO******************** | | | | 1)NOTE:SUBMIT AIC RATING OF ALL EQUIP- | | -MENT AND BREAKERS. | | 2)NOTE:GROUNDING ELECTRODE CONDUCTOR | | TO GO TO GROUND ROD AND BUILDING | | STEEL AS PER ART:250-81 | | 3)NOTE:AS PER 1996 NFPA-72 SMOKE | | DETECTORS ARE REQ`D INSIDE AND OUTSIDE | | BEDROOMS IN NEW DWELLINGS | | 4)NOTE:ALL RECEPTS.SERVING KITCHEN | | COUNTER ARE TO BE GFI/GFI PROTECTED AS | | PER ART;210-8-A-6 | | | | NEED TO HAVE THE ABOVE INFORMATION | | SUBMITTED AND APPROVED ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. |
|