Plan Review Notes
Plan Review Notes For Permit 99080073
Permit Number 99080073
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************PROVISO******************
  
 1) NOTE:AS PER 1996 NFPA-72 2-2.1.1.1
 SMOKE DETECTORS ARE REQ`D INSIDE AND
 OUTSIDE BEDROOMS ON NEW HOMES.
 2) NOTE;AS PER ART;210-8-A-6 ALL OUTLETS
 SERVING KITCHEN COUNTER SPACE ARE TO BE
 GFI/GFI PROTECTED.
 3) NOTE;OUTLET AS PER 210-52 REQ`D IN
 MASTER BEDROOM.
 4) NOTE;GROUNDING ELECTRODE CONDUCTOR
 TO GOT TO BLDG.STEEL ALSO AS PER ART;
 250-81
 5) NOTE;NEED TO SUBMIT AIC RATING OF
 ALL EQUIPMENT AND BREAKERS.AS PER ARTS;
 110-9 AND 215-5
  
 PLEASE DO ALL THE ABOVE AND HAVE
 SUBMITTED AND APPROVED BEFORE ELECTRICAL
 ROUGH INSPECTION.