Plan Review Notes
Plan Review Notes For Permit 99080039
Permit Number 99080039
Review Stop P
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00CLEARLY SHOW ON PLANS THAT THE KITCHEN
 SINK COMPLIES W/FACBC SEC.4.24.1.-
 4.24.7.
  
 A SERVICE SINK IS REQD.PER SPC TABLE 407
 FOOTNOTE #15.
  
 SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407.(DORMITORIES)AND SHALL BE HANDICAP
 ACCESSIBLE PER FACBC SEC.4.21.
  
 CLEARLY SHOW ON PLANS THAT FLOORS AND
 WALLS IN COMMON AREA BATHROOMS AND
 TOILET ROOM COMPLY W/STD.BLDG.CODE SEC.
 1204.2.
  
 FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT.
 PER PERSON (SLEEPING AREA ONLY) PER SPC
 TABLE 407.(SEE DORMITORIES).
  
 PLANS SHOW WATER CLOSETS INFRINGING ON
 WHEELCHAIR TURNING SPACE IN TOILET/BATH
 ROOMS.COMPLY W/FACBC SEC.4.2.3.
  
 SEPARATE FULLY ACCESSIBLE TOILET/BATH
 FACILITIES SHALL BE PROVIDED FOR MALES
 & FEMALES (COMMON AREA FACILITIES) PER
 FACBC SEC.4.1.3.(11), 4.22, 9.2(E).
  
 AN APPROVED BFP DEVICE IS REQD.ON THE
 MAKE-UP WATER LINE TO THE COOLING TOWER.
 SPC SEC.606.1.
  
 A GREASE INTERCEPTOR IS REQD.PER SPC
 SEC.1004.1, 1004.2, 1004.4.CONTACT ROD
 COMPO AT CITY OF W.P.B. REGIONAL WASTE-
 WATER TREATMENT PLANT FOR SIZE REQS.
 (561) 835-7423.
  
 SHT.P-8-WATER HEATER PAN DAIN AND RELIEF
 LINE SHALL NOT BE COMBINED PER COUNTY-
 WIDE AMENDMENTS TO STD.PLBG.CODE SECS..
 507.8.3, 507.8.4.
  
 OCCUPANCY SHALL BE DETERMINED BY THE
 BUILDING OFFICIAL PER SBC SEC.301.3.
 AND THE BUILDING OFFICIAL SHALL RENDER
 INTERPRETATIONS PER SBC SEC.103.1(RE:
 IS OCCUPANCY A DWELLING OR DORMITORY?)
  
 ALL ADDENDUMS TO PLANS SHALL BE ATTACHED
 TO THE PLANS