Plan Review Notes
Plan Review Notes For Permit 99080039
Permit Number 99080039
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00NOTES CORRECTED ON REVISION
 1)PROVIDE BACKDRAFT DAMPERS AT EACH
 EXHAUST FAN RUNOUT TO PREVENT CARRYOVER
 INTO ROOMS WITHOUT CEILING MOUNTED EXHAU
 ST FANS FROM ROOMS WITH CEILING MOUNTED
 EXHAUST FANS WHEN ROOF MOUNTED EXHAUST
 FANS ARE NOT RUNNING 1997 SMC 501.4
 2) IF HP-F IS USING ABOVE CEILING FOR
 RETURN AIR PLENUM, AIR ADMITTANCE VALVES
 'SHALL NOT BE USED IN SAME SPACE. SMC
 609.1.3
 3)ANY A/C UNITS SERVING AREA USED FOR
 EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE
 DETECTOR 1997 SMC 406.2
 4)EVERY ATTIC IN WHICH MECHANICAL EQUIP-
 MENT IS INSTALLED SHALL BE ACCESSIBLE BY
 AN OPENING AS LARGE AS THE LARGEST PIECE
 OF EQUIPMENT BUT IN NO CASE LESS THAN
 22X36 INCHES. 1997 SMC 304.4.1