Plan Review Notes For Permit 99080038 |
Permit Number |
99080038 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | LAUNDRY ROOM SHALL COMPLY W/F.A.C.B.C. | | SEC.9.5.1. | | | | KITCHEN AREA SHALL COMPLY W/F.A.C.B.C. | | SECS.4.24.1- 4.24.7, 9.22(7). | | | | WALLS AND FLOORS OF TOILET ROOMS SHALL | | COMPLY W/SBC SEC.1204.2. | | | | A SERVICE SINK IS REQ'D.PER TABLE 407 OF | | SPC,FOOTNOTE # 15. | | | | TOILET ROOMS SHALL BE ACCESSIBLE PER | | F.A.C.B.C.SEC.4.1.3(11).4.22.(SEPARATE | | FULLY ACCESSIBLE TOILET FACILITIES SHALL | | BE PROVIDED FOR MALES & FEMALES.)SEE | | TABLE 407(DORMITORIES) FOR FIXTURE REQS. | | | | CLEARLY SHOW WHEELCHAIR TURNING SPACE | | IN ACCESSIBLE TOILET ROOMS PER F.A.C.B.C | | SEC.4.2.3. | | | | AN APPROVED BFP DEVICE IS REQD.ON THE | | MAKEUP WATER LINE TO THE COOLING TOWER. | | SPC 606.1 . | | | | A SHOWER SHALL BE PROVIDED PER SPC TABLE | | 407(DORMITORIES) AND SHALL BE HANDICAP | | ACCESSIBLE PER F.A.C.B.C. SEC.4.21. |
|