Plan Review Notes
Plan Review Notes For Permit 99080038
Permit Number 99080038
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED
 1) PROVIDE BACKDRAFT DAMPERS AT EACH
 EXHAUST FAN RUNOUT TO PREVENT CARRYOVER
 INTO ROOMS WITHOUT CEILING MOUNTED EXHAU
 ST FANS FROM ROOMS WITH CEILING MOUNTED
 EXHAUST FANS WHEN ROOF MOUNTED EXHAUST
 FANS ARE NOT RUNNING 1997 SMC 501.4
 2) IF HP-F IS USING ABOVE CEILING FOR
 RETURN AIR PLENUM, AIR ADMITTANCE VALVES
 SHALL NOT BE USED IN SAME SPACE
 3) ANY A/C UNITS SERVING AREA USED FOR
 EGRESS SHALL BE SHUT DOWN BY DUCT SMOKE
 DETECTOR 1997 SMC 406.2
 4) EVERY ATTIC IN WHICH MECHANICAL EQUIP
 MENT IS INSTALLED SHALL BE ACCESSIBLE BY
 AN OPENING AS LARGE AS THE LARGEST PIECE
 OF EQUIPMENT BUT IN NO CASE LESS THAN
 22X36 INCHES.