Notes
Date Text
2001-01-08 00:00:00THE OCCUPANCY OF THE STRUCTURE SHALL BE
 DETERMINED BY THE BUILDING OFFICIAL PER
 SBC SEC.301.3 AND THE BUILDING OFFICIAL
 SHALL RENDER INTERPRETATIONS PER SBC
 SEC.103.1.(RE:IS OCCUPANCY TO BE CLASSED
 AS A DWELLING OR A DORMITORY.?)
  
 CLEARLY SHOW ON THE PLANS THAT THE
 KITCHEN SINK COMPLIES W/FACBC SEC.4.24.1
 THRU 4.24.7.
  
 SHOWERS SHALL BE PROVIDED PER SPC TABLE
 407(DORMITORIES) AND SHALL BE HANDICAP
 ACCESSIBLE PER SBC 4.21.
  
 CLEARLY SHOW ON THE PLANS THAT FLOORS
 AND WALLS IN COMMON AREA BATHROOMS AND
 TOILET ROOMS COMPLY W/SBC SEC.1204.2
  
 FIXTURE REQS.SHALL BE BASED ON 50 SQ.FT.
 PER PERSON (SLEEPING AREA ONLY) PER
 TABLE 407 OF SPC.
  
 SHT.M-5-AN APPROVED BACKFLOW PREVENTION
 DEVICE SHALL BE INSTALLED IN THE MAKE-UP
 WATER LINE TO THE COOLING TOWER PER SBC
 SEC.606.1-606.5
  
 A GREASE INTERCEPTOR IS REQD.PER SPC SEC
 1004.1, 1004.2.,1004.4.CONTACT RODNEY
 COMPO AT CITY OF W.P.B. REGIONAL WASTE-
 WATER TREATMENT FACILITY FOR SIZE
 REQS.
  
 SHT.P-8-WATER HEATER PAN DRAIN AND
 RELIEF LINE SHALL NOT BE COMBINED PER
 COUNTYWIDE AMENDMENTS TO STD.PLBG.CODE
 SEC.507.8.3,507.8.4.
  
 SUBMIT COPY OF COMPLETED APPLICATION OF
 WATER USE PERMIT FROM SO.FLA.WTR.MNGMT.
 (MUST HAVE AGENCY'S STAMP OF RECEIPT ON
 APPLICATION.)SPC 101.4.7,FLA.STATUTE
 373.62.
  
 CORRECTIONS TO PLANS TO BE MADE ON LARGE
 SHEETS AND ADDENDUMS SHALL BE ATTACHED
 TO THE PLANS.