Plan Review Notes For Permit 99080036 |
Permit Number |
99080036 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) THE NEW ENTRY DRIVE IS TO BE AT LEAST | | 20 FEET IN CLEAR WIDTH. | | 2) BUILDING ADDRESS NOT SHOWN ON | | ELEVATION DRAWINGS. BUILDING ADDRESS TO | | COMPLY WITH CITY CODE REQUIREMENTS. | | 3) PROVIDE COMPLETE FIRE ALARM SYSTEM | | SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT | | SHOWN ON PLANS. CUT SHEETS, WIRING | | DIAGRAM AND FLOOR PLANS ARE TO BE | | SUBMITTED. | | | | ON NOVEMBER 27,2000, WRITER SPOKE TO | | KEVIN NORTH OF THE WEITZ COMPANY. | | PER MR. NORTH, THE BUILDING WILL BE | | COMPLETELY FIRE SPRINKLER PROTECTED AND | | THE FP PLANS WERE PREVIOUSLY SUBMITTED | | TO THE CITY. MR. NORTH WAS ADVISED THAT | | THE FIRE SPRINKLER SYSTEM CONNECTION IS | | TO BE WITHIN 150 FEET OF THE FIRE | | HYDRANT. PLANS WERE PREVIOUSLY APPROVED | | BY FIRE RESCUE. | | | | CAPTAIN MIKE CARSILLO | | 659-8096,EXT.8497 | | 835-2910 |
|