Plan Review Notes
Plan Review Notes For Permit 99080036
Permit Number 99080036
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) THE NEW ENTRY DRIVE IS TO BE AT LEAST
 20 FEET IN CLEAR WIDTH.
 2) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWINGS. BUILDING ADDRESS TO
 COMPLY WITH CITY CODE REQUIREMENTS.
 3) PROVIDE COMPLETE FIRE ALARM SYSTEM
 SHOP DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON PLANS. CUT SHEETS, WIRING
 DIAGRAM AND FLOOR PLANS ARE TO BE
 SUBMITTED.
  
 ON NOVEMBER 27,2000, WRITER SPOKE TO
 KEVIN NORTH OF THE WEITZ COMPANY.
 PER MR. NORTH, THE BUILDING WILL BE
 COMPLETELY FIRE SPRINKLER PROTECTED AND
 THE FP PLANS WERE PREVIOUSLY SUBMITTED
 TO THE CITY. MR. NORTH WAS ADVISED THAT
 THE FIRE SPRINKLER SYSTEM CONNECTION IS
 TO BE WITHIN 150 FEET OF THE FIRE
 HYDRANT. PLANS WERE PREVIOUSLY APPROVED
 BY FIRE RESCUE.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910