Plan Review Notes
Plan Review Notes For Permit 99080036
Permit Number 99080036
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00INDICATE NUMBER OF STAFF TO BE PRESENT
 AT ANY ONE TIME.SPC 104.2.1,TABLE 407.
  
 A GREASE INTERCEPTOR SHALL BE REQUIRED
 PER SPC SEC.1004.1,1004.4.
 CONTACT RODNEY COMPO AT CITY OF WEST
 PALM BEACH REGIONAL SEWER TREATMENT
 PLANT AT 835-7423 FOR MIN.SIZE REQS.
  
 SHT.A-5-SHOW ALL DIMENSIONS AND HEIGHT
 REQ'S.FOR THE HANDICAP FIXTURES.COMPLY
 W/FLA.ACCESS.CODE FOR BLDG.CONST.10/97
 EDITION.
  
 SHT.M-5-AN APPROVED BACKFLOW PREVENTION
 DEVICE SHALL BE INSTALLED ON THE MAKE-UP
 WATER LINE T0 THE COOLING TOWER PER SPC
 SEC.606.1-606.5(WHERE APPLICABLE).
  
 WET VENTS SHALL RECEIVE THE DISCHARGE
 FROM FIXTURE DRAINS ONLY PER COUNTYWIDE
 AMENDMENTS SEC.911.1.1.(RMS.123A & 132A)
  
 SHT.P-3-RMS.#125,127,128,130. SINK S-1
 IS NOT SHOWN ON WATER RISER.SPC 104.2.1.
  
 SHT.P-8.DETAIL #1-PAN DRAIN & RELIEF
 LINES SHALL BE RUN SEPARATELY TO POINT
 OF DISCHARGE.SPC SEC.507.8.3,507.8.4.
  
 A WATER USE PERMIT IS REQ'D.FOR THE
 IRRIGATION SYSTEM PER FLA.STATUTE 373.62
  
 SHT.C-1.CLEANOUTS ON SANITARY SEWER
 SHALL COMPLY W/SPC SEC.710.2.4(2).
  
 AN APPROVED BFP DEVICE IS REQ'D.ON THE
 DOMESTIC WATER SERVICE TO THE BLDG.PER
 SPC 606.1.
  
 IRRIGATION PLANS SHALL BE SIGNED AND
 SEALED BY DESIGN PROFESSIONAL.
  
 TOILET ROOM FLOORS AND WALLS SHALL
 COMPLY W/SBC SEC.1204.2.
  
 KIT.AREA SHALL COMPLY W/F.A.C.B.C.SECS.
 4.24.1- 4.24.7,9.22(7).
  
 LAUNDRY AREA SHALL COMPLY W/F.A.C.B.C.
 SEC.9.5.1.
  
 WATER AND SANITARY LINES AT DUMPSTER
 AREA SHALL BE SHOWN ON THE APPROPRIATE
 RISER DIAGRAMS.SPC 104.2.1.
  
 DRAIN FROM DUMPSTER AND CAN WASH SHALL
 DISCHARGE THROUGH GREASE INTERCEPTOR.
 SPC 1004.1,1004.4.